Model 3PT3-60 Indoor Voltage Transformer

ACCURACY CLASS:
0.3 WX, 06M, 1.2Y at 100% rated voltage
with 120V based ANSI burden.
STANDARD SECONDARY VOLTAGE:
120 volts
FREQUENCY:
60 Hz.
MAXIMUM SYSTEM VOLTAGE:
5.6 kV, BIL 60kV full wave
THERMAL RATING:
500 VA, ( 2.4 secondary amps per phase), 60 Hz at 30° C. amb.
350 VA ( 1.7 secondary amps per phase ), 60 Hz at 55° C. amb.
WEIGHT:
Approximately 38 lbs.
1


1 Features
1 Primary terminals are No. 10-32 brass screws with one flatwasher and lockwasher.
1 The core and coil assembly is encased in a plastic enclosure and vacuum encapsulated in polyurethane resin.
1 The transformers are tested for partial discharge to Canadian Standards CAN 3-C13-M83. This test can also be carried out to IEC requirements if requested.
1 Recommended Spacing is for guidance only. The user needs to set appropriate values to assure performance for: high potential test; impulse test; high humidity; partial discharge; high altitude.

©2003 - 2010 Panel Components & Systems, Inc. | All Rights Reserved | Website Designed by: Computer Doctors Website Design