Model 546 Current Transformer

FEATURES:

1.10" ID

1 Used for Ammeter and Energy Control Applications
1 Frequency 50 - 400 HZ. Insulation Class 0.6 KV BIL 10 KV
1 Molded thermoplastic housing. Optional Mounting Bracket and Plate available.
1 Conforms to ANSI C57.13 and applicable IEC standards.
1 Secondary is available with 5VDC, 10VAC and 5VAC rating.
1 Choice of either 8-32 Screw Terminals or 16 AWG Lead Wires.
1 Available as U.L. Recognized Component File E100575, contact factory for information.
1 Other primary current ratings, up to 400A are available upon request.

Part Number Ratio ACCURACY @ 60HZ NOMINAL SECONDARY WINDING
RESISTANCE (OHMS)
± % BURDEN (VA)
546-050-00 50:5A 2.0 1.0 0.010
546-060-00 60:5A 2.0 1.5 0.012
546-075-00 75:5A 2.0 2.0 0.015
546-100-00 100:5A 1.0 2.0 0.020
546-120-00 120:5A 1.0 2.5 0.024
546-150-00 150:5A 1.0 3.5 0.029
546-200-00 200:5A 1.0 5.0 0.039
546-300-00 300:5A 1.0 10.0 0.058
546-400-00 400:5A 1.0 12.5 0.077
Current Transformers - Model 546
Note: All Dimensions in inches

©2003 - 2010 Panel Components & Systems, Inc. | All Rights Reserved | Website Designed by: Computer Doctors Website Design